Bottom price American Box Transformer Substation - YB-12/0.4 Outdoor Preinstalled Type Substation (Ou) – Pengbian
Bottom price American Box Transformer Substation - YB-12/0.4 Outdoor Preinstalled Type Substation (Ou) – Pengbian Detail:
Conditions of use
Altitude does not exceed 1000 m;
Ambient temperature: – 25 ℃ ~ + 40 ℃;
Relative humidity: day average no greater than 95%, the monthly average no greater than 90%;
Mounting ambicnt: no fire and explosion danger, conductive dust, chemical corrosive gas and the site of violent vibration, if beyond the above conditions, the user can negotiate with our company.
Function and characteristics of the
Integrated HV switchgear, transformer and LV switchgear, endowing strong integrity;
Perfect HV and LV protection, safe and reliable operation, simple maintenance;
Less land occupation, less investment, short production cycle and convenient movement; flexible and diverse wiring schemes; unique structure;
Firm and unique honeycomb structure double-layer (composite board) shell:
Heat-insulated, heat-dissipating and ventilated, beautiful, with high protection grade. The shell material can be stainless steel iron alloy, aluminum alloy, cold rolled plate and color steel plate.
There are many types: general, villa, compact and so on.
FTU can be equipped in the high pressure ring network cabinet to realize reliable detection of short circuit and single-phase ground fault;it has the function of “four remote” to facilitate automatic upgrade of distribution network.
Types of meaning
Load switch technology parameters
The name of the |
unit |
FN12-12 Load switch |
FZM12-12 The vacuum load switch |
The rated voltage |
kV |
10 |
|
The highest working voltage |
kV |
12 |
|
Rated frequency |
|
50 |
|
Rated current |
|
630 |
|
The breaking load rated current |
A |
630 |
|
The thermal stability of current (RMS) |
kA/S |
20/2 |
20/4 |
Dynamic stability of current |
kA |
50 |
50 |
Short circuit close current (peak value) |
kA |
50 |
50 |
At full open circuit |
time |
20 |
10000 |
Mechanical life |
time |
2000 |
10000 |
1 min power frequency withstand voltage (alternate with and over the ground) |
kV |
42 |
42 |
Lightning impulse voltage (relative on the ground) |
kV |
75 |
75 |
High voltage fuse technology parameters
The serial number |
Rated voltage (KV) |
The Breaking current(A) |
Breaking current (KA)
|
The melt rated current (A) |
|
The British model |
Domestic models |
||||
SDW*J |
12 |
40 |
31.5 |
6.3,10,16,20,25,31.5,40 |
|
SFL*J |
XRNT-12 |
12 |
100 |
31.5 |
50,63,71,80,100 |
SKW*J |
12 |
125 |
31.5 |
125 |
* note: be determined by whether to install the impactor, N for no firing pin, A firing pin.
Product detail pictures:
Related Product Guide:
Cooperation
Dedicated to strict top quality command and considerate purchaser support, our experienced staff customers are always available to discuss your necessities and be certain full client gratification for Bottom price American Box Transformer Substation - YB-12/0.4 Outdoor Preinstalled Type Substation (Ou) – Pengbian , The product will supply to all over the world, such as: Mumbai , Ukraine , Mongolia , Each product is carefully made, it will make you satisfied. Our merchandise in the production process have got strictly monitored, because it is only to supply you the best quality, we'll feel confident. High production costs but low prices for our long-term cooperation. You can have a variety choices and the value of all types are same reliable. If you have any question, do not hesitate to ask us.