Types of meaning
S13-M series 10 kv three-phase double winding excitation regulating distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) 4.0 |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
30 |
6 6.3 6.6 10 10.5 11 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yzn11 Yyno |
80 |
630/660 |
1.2 |
4.0 |
50 |
100 |
910/870 |
1.0 |
|||||
63 |
110 |
1090/1040 |
0.95 |
|||||
80 |
130 |
1310/1250 |
0.95 |
|||||
100 |
150 |
1580/1500 |
0.90 |
|||||
125 |
170 |
1890/1800 |
0.90 |
|||||
160 |
200 |
2310/2200 |
0.80 |
|||||
200 |
240 |
2730/2600 |
0.80 |
|||||
250 |
290 |
3200/3050 |
0.70 |
|||||
315 |
340 |
3830/3650 |
0.70 |
|||||
400 |
410 |
4520/4300 |
0.65 |
|||||
500 |
480 |
5410/5150 |
0.65 |
|||||
630 |
Dyn11 Yyno |
570 |
6200 |
0.45 |
4.5 |
|||
800 |
700 |
7500 |
0.45 |
|||||
1000 |
830 |
10300 |
0.45 |
|||||
1250 |
970 |
12000 |
0.40 |
|||||
1600 |
1170 |
14500 |
0.40 |
|||||
2000 |
1550 |
18300 |
0.30 |
5.0 |
||||
2500 |
1830 |
21200 |
0.30 |
e: for the rated capacity of 500 kva and below transformer, load loss value of the diagonal lines in the table above apply to Dyn11 or Yzn11 link group, slash at the bottom of the load loss value applies to Yyno link group.
S13-M series of 20 kv three-phase double winding non-field excitation changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
30 |
20 22 24 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yzn11 Yyno |
80 |
690/660 |
2.1 |
5.5 |
50 |
100 |
1010/960 |
2 |
|||||
63 |
110 |
1200/1150 |
1.9 |
|||||
80 |
130 |
1440/1370 |
1.8 |
|||||
100 |
150 |
1730/1650 |
1.6 |
|||||
125 |
170 |
2080/1980 |
1.5 |
|||||
160 |
200 |
2540/2420 |
1.4 |
|||||
200 |
240 |
3000/2860 |
1.3 |
|||||
250 |
290 |
3520/3350 |
1.20 |
|||||
315 |
340 |
4210/4010 |
1.10 |
|||||
400 |
410 |
4970/4730 |
100 |
|||||
500 |
480 |
5940/5660 |
1.00 |
|||||
630 |
570 |
6820 |
0.90 |
6.0 |
||||
800 |
700 |
8250 |
0.80 |
|||||
1000 |
830 |
11330 |
0.70 |
|||||
1250 |
970 |
13200 |
0.70 |
|||||
1600 |
1170 |
15950 |
0.60 |
|||||
2000 |
1550 |
19140 |
0.60 |
|||||
2500 |
1830 |
22220 |
0.50 |
S13-M series of 35 kv three-phase double winding non-field excitation changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
50 |
35 38.5 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
130 |
1200/1140 |
1.05 |
6.5 |
100 |
185 |
2010/1910 |
0.90 |
|||||
125 |
215 |
2370/2260 |
0.90 |
|||||
160 |
225 |
2820/2680 |
0.80 |
|||||
200 |
270 |
3320/3160 |
0.80 |
|||||
250 |
320 |
3950/3760 |
0.75 |
|||||
315 |
380 |
4750/4530 |
0.75 |
|||||
400 |
460 |
5740/5470 |
0.65 |
|||||
500 |
540 |
6910/6580 |
0.65 |
|||||
630 |
660 |
7860 |
0.50 |
|||||
800 |
780 |
9400 |
0.50 |
|||||
1000 |
920 |
11500 |
0.50 |
|||||
1250 |
1120 |
13900 |
0.45 |
|||||
1600 |
1350 |
16600 |
0.45 |
|||||
2000 |
1590 |
19700 |
0.40 |
|||||
2500 |
1890 |
23200 |
0.40 |
Note: for the rated capacity of 500 kva and below transformer, load loss value of the diagonal lines in the table above apply to Dyn11 or Yzn11 link group, slash at the bottom of the load loss value applies to Yyno link group.
Product detail pictures:
Related Product Guide:
Cooperation
We have many excellent staff members good at marketing, QC, and dealing with kinds of troublesome problem in the production process for Factory For Pad Mounted Substation - S13 Series Of Oil-Immersed Transformer – Pengbian , The product will supply to all over the world, such as: Guyana , Netherlands , Malaysia , Our factory covers an area of 12,000 square meters, and has a staff of 200 people, among which there are 5 technical executives. We are specialized in producing.We have rich experience in export. Welcome to contact us and your enquiry will be replied as soon as possible.
By Charlotte from Australia - 2018.02.04 14:13
This enterprise in the industry is strong and competitive, advancing with the times and develop sustainable, we are very pleased to have a opportunity to cooperate!
By Martha from Kenya - 2018.08.12 12:27