Good Quality S11 Series Of Oil-Immersed Transformer - 35Kv Oil Immersed Transformer – Pengbian
Good Quality S11 Series Of Oil-Immersed Transformer - 35Kv Oil Immersed Transformer – Pengbian Detail:
Product standards
GB1094.1~2-2013 GB/T 6451-2015
High pressure rating: 10 (10.5, 11, 6, 6.3, 6.6) kV
Low pressure rating: 0.4 kV
Tapping range: non-field excitation changer
(5% plus or minus 5%, plus or minus 2 x2.)
On-load voltage regulation: (plus or minus 4 x2. 5%)
Link category: Dyn11 or Yyn0
Insulation level: LI75AC35 / AC5
Product parameter
Types of meaning
S11-M series 10kV three – phase double – winding non – excitation voltage regulator distribution transformer
Rated capacity(kVA) |
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
30 |
6 6.3 6.6 10 10.5 11 |
±5X2.5±5 |
0.4 |
Dyn11 Yzn11 YynO |
100 |
630/600 |
1.5 |
4.0 |
50 |
130 |
910/870 |
1.3 |
|||||
63 |
150 |
1090/1040 |
1.2 |
|||||
80 |
180 |
1310/1250 |
1.2 |
|||||
100 |
200 |
1580/1500 |
1.1 |
|||||
125 |
240 |
1890/1800 |
1.1 |
|||||
160 |
280 |
2310/2200 |
1.0 |
|||||
200 |
340 |
2730/2600 |
1.0 |
|||||
250 |
400 |
3200/3050 |
0.90 |
|||||
315 |
480 |
3830/3650 |
0.90 |
|||||
400 |
570 |
4520/4300 |
0.80 |
|||||
500 |
680 |
5410/5150 |
0.80 |
|||||
630 |
Dyn11 YynO |
810 |
6200 |
0.60 |
4.5 |
|||
800 |
980 |
7500 |
0.60 |
|||||
1000 |
1150 |
10300 |
0.60 |
|||||
1250 |
1360 |
12000 |
0.50 |
|||||
1600 |
1640 |
14500 |
0.50 |
|||||
2000 |
1940 |
18300 |
0.40 |
5.0 |
||||
2500 |
2290 |
21200 |
0.40 |
Note 1: For transformers rated 500 kVA or less, the load loss values above the slash in the table apply to the Dyn11 or Yzn11 junction group, and the load loss values below the slash apply to the Yyno junction group.
S11 series 10kV three – phase dual – winding non – excitation voltage regulator power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
630 |
6 6.3 6.6 10 10.5
|
±2X2.5±5 |
3 3.15 6.3 |
Yd11 Dyn11
|
820 |
6920 |
0.6 |
5.5 |
800 |
1000 |
8460 |
0.6 |
|||||
1000 |
1180 |
9910 |
0.6 |
|||||
1250 |
1400 |
11700 |
0.5 |
|||||
1600 |
1680 |
14100 |
0.4 |
|||||
2000 |
2010 |
16900 |
0.4 |
|||||
2500 |
2370 |
19600 |
0.4 |
|||||
3150 |
2800 |
23000 |
0.4 |
|||||
4000 |
3.15 6.3 |
3450 |
27300 |
0.4 |
||||
5000 |
4100 |
31300 |
0.4 |
|||||
6300 |
4890 |
35000 |
0.4 |
SZ11-M series 10kV three-phase double-winding on-load tap-changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
200 |
6 6.3 10 10.5
|
±4X2.5 |
0.4
|
Dyn11 Yyn0
|
380 |
2900 |
1.00 |
4.0 |
250 |
440 |
3420 |
0.90 |
|||||
315 |
530 |
4100 |
0.90 |
|||||
400 |
640 |
4950 |
0.80 |
|||||
500 |
760 |
5890 |
0.80 |
|||||
630 |
960 |
7260 |
0.60 |
4.5 |
||||
800 |
1120 |
8890 |
0.60 |
|||||
1000 |
1360 |
10400 |
0.60 |
|||||
1250 |
1560 |
12300 |
0.50 |
|||||
1600 |
1920 |
14700 |
0.50 |
|||||
2000 |
2270 |
18600 |
0.40 | 5.0 | ||||
2500 |
2680 |
21600 |
0.4 |
Note 1: Rated capacity 500KVA and below transformer, the load loss above the oblique line in the table applies to Dyn11 or Yzn11; the load loss below the oblique line applies to Yyn0.
S11 – M series 20 kv three-phase double-winding non-field excitation changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo(w) |
No-load current (%) |
Short circuit impedance (%) |
No-load current(%) |
Short circuit impedance(%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
30 |
20 22 24
|
±5% ±2×2.5% |
0.4 |
Dyn11 Yzn11 Yyno |
100 |
690/660 |
2.1 |
5.5 |
50 |
130 |
1010/960 |
2 |
|||||
63 |
150 |
1200/1150 |
1.9 |
|||||
80 |
180 |
1440/1370 |
1.8 |
|||||
100 |
200 |
1730/1650 |
1.6 |
|||||
125 |
240 |
2080/1980 |
1.5 |
|||||
160 |
280 |
2540/2420 |
1.4 |
|||||
200 |
340 |
3000/2860 |
1.3 |
|||||
250 |
400 |
3520/3350 |
1.20 |
|||||
315 |
480 |
4210/4010 |
1.10 |
|||||
400 |
570 |
4970/4730 |
1.00 |
|||||
500 |
680 |
5940/5660 |
1.00 |
|||||
630 |
810 |
6820 |
0.90 |
6.0 |
||||
800 |
980 |
8250 |
0.80 |
|||||
1000 |
1150 |
11330 |
0.70 |
|||||
1250 |
1380 |
13200 |
0.70 |
|||||
1600 |
1650 |
15950 |
0.60 |
|||||
2000 |
1950 |
19140 |
0.60 |
|||||
2500 |
2340 |
22220 |
0.50 |
S11 series 35 kv three-phase double-winding non-field excitation changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
50 |
35 38.5 |
±5 ±2×2.5% |
0.4 |
Dyn11 YynO |
160 |
1200/1140 |
1.30 |
6.5 |
100 |
230 |
2010/1910 |
1.10 |
|||||
125 |
270 |
2370/2260 |
1.10 |
|||||
160 |
280 |
2820/2680 |
1.00 |
|||||
200 |
340 |
3320/3160 |
1.00 |
|||||
250 |
400 |
3950/3760 |
0.95 |
|||||
315 |
480 |
4750/4530 |
0.95 |
|||||
400 |
580 |
5740/5470 |
0.85 |
|||||
500 |
680 |
6910/6580 |
0.85 |
|||||
630 |
830 |
7860 |
0.65 |
|||||
800 |
980 |
9400 |
0.65 |
|||||
1000 |
1150 |
11500 |
0.65 |
|||||
1250 |
1400 |
13900 |
0.60 |
|||||
1600 |
1690 |
16600 |
0.60 |
|||||
2000 |
1990 |
19700 |
0.55 |
|||||
2500 |
2360 |
23200 |
0.55 |
Note 1: Rated capacity 500KVA and below transformer, the load loss above the oblique line in the table applies to Dyn11 or Yzn11; the load loss below the oblique line applies to Yyn0.
S11 series 35kV three – phase double – winding group non – excitation voltage regulator power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
50 |
35 38.5 |
±5 ±2×2.5% |
0.4 |
Dyn11 YynO |
160 |
1200/1140 |
1.30 |
6.5 |
100 |
230 |
2010/1910 |
1.10 |
|||||
125 |
270 |
2370/2260 |
1.10 |
|||||
160 |
280 |
2820/2680 |
1.00 |
|||||
200 |
340 |
3320/3160 |
1.00 |
|||||
250 |
400 |
3950/3760 |
0.95 |
|||||
315 |
480 |
4750/4530 |
0.95 |
|||||
400 |
580 |
5740/5470 |
0.85 |
|||||
500 |
680 |
6910/6580 |
0.85 |
|||||
630 |
830 |
7860 |
0.65 |
|||||
800 |
980 |
9400 |
0.65 |
|||||
1000 |
1150 |
11500 |
0.65 |
|||||
1250 |
1400 |
13900 |
0.60 |
|||||
1600 |
1690 |
16600 |
0.60 |
|||||
2000 |
1990 |
19700 |
0.55 |
|||||
2500 |
2360 |
23200 |
0.55 |
Note: For transformers with a low voltage of 10.5 kVA, products with a link group designation of DYn11 are available with a rated capacity of 3150 kvA and above and a -5% tap position for maximum current tapping.
SZ11 series 35kV three – phase double – winding on – load voltage regulator power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
630 |
35 |
±2*2.5% ± 5% |
3.15 6.3 10.5 |
Yd11 |
830 |
7860 |
0.65 |
6.5 |
800 |
980 |
9400 |
0.65 |
|||||
1000 |
1150 |
11500 |
0.65 |
|||||
1250 |
1400 |
13900 |
0.55 |
|||||
1600 |
1690 |
16600 |
0.45 |
|||||
2000 |
2170 |
18300 |
0.45 |
|||||
2500 |
2560 |
19600 |
0.45 |
|||||
3150 |
35-38.5 |
±2X2.5%±5% |
3.15 6.3 10.5 |
3040 |
23000 |
0.45 |
7.0 |
|
4000 |
3610 |
27300 |
0.45 |
|||||
5000 |
4320 |
31300 |
0.45 |
|||||
6300 |
5240 |
35000 |
0.45 |
8.0 |
||||
8000 |
35-38.5 |
±2^2.5% |
3 15 3.3 6.3 6.6 10.5 |
YNd11 |
7200 |
38400 |
0.35 |
|
10000 |
8700 |
45300 |
0.35 |
|||||
12500 |
10000 |
53800 |
0.3 |
|||||
16000 |
12100 |
65800 |
0.3 |
|||||
20000 |
14400 |
79500 |
0.3 |
|||||
25000 |
17000 |
94000 |
0.25 |
10.0 |
||||
31500 |
20200 |
112000 |
0.25 |
Note: for low voltage of 10.5 kVA transformer, can provide link group of products labeled DYn11. – 7.5% tap position for maximum current tap.
Product detail pictures:
Related Product Guide:
Cooperation
Our company since its inception, constantly regards product or service high quality as business life, continually improve creation technology, make improvements to product high-quality and consistently strengthen business total high-quality management, in strict accordance together with the national standard ISO 9001:2000 for Good Quality S11 Series Of Oil-Immersed Transformer - 35Kv Oil Immersed Transformer – Pengbian , The product will supply to all over the world, such as: Cambodia , South Africa , Guatemala , After years' creating and developing, with the advantages of trained qualified talents and rich marketing experience, outstanding achievements were gradually made. We get good reputation from the customers due to our good products quality and fine after-sale service. We sincerely wish to create a more prosperous and flourishing future together with all the friends home and abroad!
By Caroline from Peru - 2017.06.29 18:55
This is a very professional and honest Chinese supplier, from now on we fell in love with the Chinese manufacturing.
By Ella from Spain - 2017.06.19 13:51