High Quality Cksc Series Resin Insulation Dry-Type Core Series Reactor - SC(ZB) Series Dry Type Transformer – Pengbian
High Quality Cksc Series Resin Insulation Dry-Type Core Series Reactor - SC(ZB) Series Dry Type Transformer – Pengbian Detail:
Product features
Low loss, low operation cost and obvious energy saving effect;
Flame retardant, fireproof, explosion-proof and pollution-free;
Good moisture-proof performance, strong heat dissipation capability;
Low partial discharge, small noise, maintenance-free;
High mechanical strength, strong short circuit resistance and long service life;
Range of application
This product is widely used in high-rise buildings, commercial complexes, hospitals, laboratories, schools, theaters, offshore drilling platforms, ships, petrochemical plants, stations, airports, subways, mines, hydro-thermal power stations, substations and so on.
Core
The iron core is made of high-quality oriented cold rolled silicon steel sheet material, with 45-degree fully inclined seam structure; the core leg is bound with insulating tape, sealed with insulating resin paint on the surface to prevent moisture and rust; clampings and fasteners are surface treated to prevent rust.
Low pressure foil coil
For low-voltage and high-current coils, the short-circuit stress during short-circuit is relatively large, and the number of low-voltage turns is relatively small. The bigger low-voltage current is, the more prominent the problem of unstable ampere turns is when winding form is adopted, and the heat dissipation problem shall also be emphatically considered. At this time, foil winding for low-voltage can better solve the above problem. First, foil product does not have axial turns and axial winding helix angle; its ampere turns of the high-voltage and low-voltage windings are balanced, and the axial stress of the transformer during short-circuit is relatively small. Second, due to its thin insulation, it is easy to set up multi-layer air ducts in the process, thus the heat dissipation problem can be better solved.
Hv casted winding
The coil uses F-class insulated copper conductor as conductor, glass fiber and epoxy resin composite material as insulation; its expansion coefficient is similar to that of copper conductor, and it has good impact resistance, temperature change resistance and crack resistance. All components of glass fiber and epoxy resin are self-extinguishing, and will not keep burning, nor will they produce toxic gases and pollute the environment. Epoxy resin has good insulation characteristics and is especially suitable for making coils with high voltage level.
Temperature control
All transformers are equipped with overheat protection device which realizes transformer temperature detection and control via the Pt thermistor embedded in LV coil. The device can provide the following functions:
1. Display the temperature value of the three-phase winding in cycle during the operation of transformer;
2. Display the temperature value of the hottest phase winding;
3. Audible and visual warning, fan startup;
4. Fan overload protection and computer interface.
Cooling way
The cooling methods of dry-type transformer are divided into natural air cooling (AN) and forced air (AF) cooling. When natural air cooling (AN) is adopted, rated capacity can be continuously output. When forced air cooling (AF) is adopted, the output of transformer can exceed 40% of the rated load on the nameplate. It is suitable for various emergency loads or short-term load operation. Long-term continuous overload operation of forced air cooling (AF) is not recommended due to large load loss and impedance voltage increase. Operation of transformer requires an appropriate ventilation volume.
When the transformer is installed in basement or in an environment with poor ventilation, a heat dissipation ventilation device must be added. The ventilation volume is selected according to the air volume loss of 2-4m/min per 1kW.
Protect shell and line bus
Dry-type transformers generally have no enclosure protection, i.e. IP00. Enclosures with IP20, IP23 and other protection grade requirements can be added as required by the user.
IP20 enclosure can prevent solid foreign matter with diameter larger than 12 mm from entering, providing safety guarantee for live parts.
IP23 also has the function of preventing water droplets from flowing in in an angle of 60 degrees with the heavy straight line, and is suitable for outdoor operation.
IP23 enclosure will reduce the cooling capacity of transformer by about 5% for small capacity and by about 10% for large capacity.
Enclosure materials include steel plate painted, aluminum alloy and stainless steel. When the enclosure is made of steel plate, the user can choose color of the enclosure.
The low-voltage outgoing line can use standard bus outgoing line, either from side or top, or special outgoing line mode can be designed as required by the user.
Using the environment
Ambient temperature: – 5 ℃ ~ + 40 ℃
The most thermidor average temperature + 30 ℃
The hottest year average temperature 20 ℃ +
The altitude does not exceed 1000 m
The power supply voltage waveform similar to sine wave
Three-phase power supply voltage should be roughly symmetric
No obvious the filth of the installation environment
Indoor use
The way into the line diagram
For distribution transformers, conventional outgoing lines, standard enclosed bus outgoing lines and standard side outgoing lines can be manufactured according to different interface forms, or special outgoing lines can be designed as required by the user.
Product parameter
Types of meaning
Product standards
GB/T10228-2015 GB1094.11-2007
High pressure rating: 10 (10.5, 11, 6, 6.3, 6.6) kV
Low pressure rating: 0.4 kV
Tapping range: no excitation voltage regulation (±5%,±2 x2.5%)
Link category: Dyn11 or Yyn0
Insulation level: LI75AC35 / AC5
SC(B)10 series10kV class non-excitation voltage regulating distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) 4.0 |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
315 |
6 6.3 6.6 10 10.5 11 |
±4×2.5 |
0.4 |
Dyn11 YynO |
990 |
3150 |
1.1 |
4.0 |
400 |
1120 |
3730 |
1.1 |
|||||
500 |
1290 |
4560 |
1.1 |
|||||
630 |
1440 |
5550 |
1.0 |
6.0 |
||||
800 |
1710 |
6550 |
1.0 |
|||||
1000 |
1980 |
7670 |
0.85 |
|||||
1250 |
2340 |
9080 |
0.85 |
|||||
1600 |
2720 |
10830 |
0.85 |
|||||
2000 |
3420 |
13280 |
0.70 |
|||||
2500 |
3960 |
15810 |
0.70 |
SC(ZB)10 series 10kV class on-load voltage regulating distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) 4.0 |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
315 |
6 6.3 6.6 10 10.5 11 |
±4×2.5 |
0.4 |
Dyn11 Yyn0 |
990 |
3150 |
1.1 |
4.0 |
400 |
1120 |
3730 |
1.1 |
|||||
500 |
1290 |
4560 |
1.1 |
|||||
630 |
1440 |
5550 |
1.0 |
6.0 |
||||
800 |
1710 |
6550 |
1.0 |
|||||
1000 |
1980 |
7670 |
0.85 |
|||||
1250 |
2340 |
9080 |
0.85 |
|||||
1600 |
2720 |
10830 |
0.85 |
|||||
2000 |
3420 |
13280 |
0.70 |
|||||
2500 |
3960 |
15810 |
0.70 |
SC(B)10 series 10kV class non-excitation voltage regulating power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) 4.0 |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
630 |
6 6.3 6.6 10 10.5 11
|
±2×2.5 ±5
|
3 3.15 6 6.3
|
Dyn11 Yd11 YynO |
1140 |
5550 |
1.0 |
6.0 |
800 |
1620 |
6640 |
1.0 |
|||||
1000 |
1940 |
7670 |
0.85 |
|||||
1250 |
2340 |
9080 |
0.85 |
|||||
1600 |
2790 |
11090 |
0.85 |
|||||
2000 |
3600 |
13280 |
0.70 |
|||||
2500 |
4230 |
15500 |
0.70 |
|||||
3150 |
5040 |
18250 |
0.60 |
|||||
4000 |
10 10.5 11
|
6030 |
21920 |
0.60 |
7.0 |
|||
5000 |
7200 |
25940 |
0.50 |
|||||
6300 |
8500 |
30830 |
0.50 |
SC(B)10 series 20kV class non – excitation voltage regulator distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) 4.0 |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
50 |
20 22 24
|
±5 ±2×2.5%
|
0.4 |
Dyn11 Yyn0
|
340 |
1070 |
2 |
6 |
100 |
540 |
1740 |
1.8 |
|||||
160 |
670 |
2160 |
1.5 |
|||||
200 |
730 |
2570 |
1.5 |
|||||
250 |
840 |
2990 |
1.3 |
|||||
315 |
970 |
3560 |
1.3 |
|||||
400 |
1150 |
4230 |
1.1 |
|||||
500 |
1350 |
5060 |
1.1 |
|||||
630 |
1530 |
5970 |
1.0 |
|||||
800 |
1750 |
7210 |
1.0 |
|||||
1000 |
2070 |
8540 |
0.85 |
|||||
1250 |
2380 |
10040 |
0.85 |
|||||
1600 |
2790 |
12050 |
0.85 |
|||||
2000 |
3240 |
15550 |
0.7 |
8 |
||||
2500 |
3870 |
18520 |
0.7 |
SC(B)10 series 35kv non-excited tap-changing transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) 4.0 |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
50 |
35 36 37 38.5 |
±2.5 ±5 |
0.4 |
Dyn11 Yyn0
|
450 |
1240 |
2.3 |
6.0 |
100 |
630 |
1830 |
2 |
|||||
160 |
790 |
2450 |
1.5 |
|||||
200 |
±5 ±2×2.5%
|
880 |
2900 |
1.5 |
||||
250 |
990 |
3320 |
1.3 |
|||||
315 |
1170 |
3940 |
1.3 |
|||||
400 |
1370 |
4720 |
1.1 |
|||||
500 |
1620 |
5810 |
1.1 |
|||||
630 |
1660 |
6720 |
1.0 |
|||||
800 |
2160 |
7970 |
1.0 |
|||||
1000 |
2430 |
9080 |
0.75 |
|||||
1250 |
2830 |
11090 |
0.75 |
|||||
1600 |
3240 |
13450 |
0.75 |
|||||
2000 |
3820 |
15900 |
0.75 |
|||||
2500 |
4450 |
19040 |
0.75 |
SC(B)10 series 35kV Non – Excitation Voltage Regulating Power Transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
75℃Load loss |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
800 |
35 36 37 38.5 |
±2×2.5 ±5 |
3.15 6 6.3 10 10.5 11 6 |
Dyn11 Yd11 Yyn0 |
2250 |
8210 |
0.95 |
6 |
1000 |
2670 |
9520 |
0.95 |
|||||
1250 |
3130 |
11270 |
0.85 |
|||||
1600 |
3690 |
13450 |
0.85 |
|||||
2000 |
4230 |
15900 |
0.75 |
7 |
||||
2500 |
4860 |
19040 |
0.75 |
|||||
3150 |
6030 |
21400 |
0.7 |
8 |
||||
4000 |
7020 |
25680 |
0.7 |
|||||
5000 |
8370 |
30480 |
0.6 |
|||||
6300 |
9900 |
35630 |
0.6 |
|||||
8000 |
Dyn11 Yd11 YNd11 |
11300 |
40170 |
0.5 |
9 |
|||
10000 |
12900 |
48470 |
0.5 |
|||||
12500 |
6 6.3 10 10.5 11 |
15700 |
56420 |
0.4 |
||||
16000 |
19300 |
66380 |
0.4 |
|||||
20000 |
22900 |
74670 |
0.35 |
10 |
||||
25000 |
27100 |
88210 |
0.35 |
SCZ10 series 35 kv level on-load voltage regulating power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
75℃Load loss |
No-load |
Short circuit impedance (%) |
||
current |
||||||||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
(%) |
|||||
2000 |
35 36 37 38.5 |
±4×2.5 |
6 6.3 10 10.5 11 |
Dyn11 Yd11 |
4500 |
16590 |
0.75 |
7.0 |
2500 |
5220 |
19740 |
0.75 |
|||||
3150 |
6300 |
22180 |
0.7 |
8.0 |
||||
4000 |
7380 |
26550 |
0.7 |
|||||
5000 |
8730 |
31530 |
0.6 |
|||||
6300 |
10300 |
36510 |
0.6 |
|||||
8000 |
11800 |
41480 |
0.5 |
9.0 |
||||
10000 |
13500 |
49870 |
0.5 |
|||||
12500 |
16400 |
58080 |
0.4 |
|||||
16000 |
20200 |
68300 |
0.4 |
|||||
20000 |
23800 |
76860 |
0.35 |
10.0 |
||||
25000 |
28100 |
90830 |
0.35 |
SC(B)11 series 10kV class non – excitation voltage regulator distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
75℃Load loss |
No-load current (%) |
Short circuit impedance (%) |
Sound level |
weight (kg) |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||||
160 |
6 6.3 6.6 10 10.5 11 |
±2×2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
490 |
1870 |
1.2 |
4 |
45 |
690 |
200 |
560 |
2220 |
1 |
45 |
980 |
|||||
250 |
650 |
2420 |
1 |
45 |
920 |
|||||
315 |
790 |
3050 |
0.9 |
46 |
1060 |
|||||
400 |
880 |
3500 |
0.9 |
46 |
1260 |
|||||
500 |
1040 |
4290 |
0.9 |
48 |
1550 |
|||||
630 |
1170 |
5240 |
0.75 |
6 |
48 |
1790 |
||||
800 |
1370 |
6110 |
0.75 |
48 |
2180 |
|||||
1000 |
1590 |
7140 |
0.75 |
50 |
2550 |
|||||
1250 |
1880 |
8510 |
0.75 |
50 |
3000 |
|||||
1600 |
2210 |
10290 |
0.75 |
50 |
3550 |
|||||
2000 |
2750 |
12690 |
0.6 |
50 |
3650 |
|||||
2500 |
3240 |
15080 |
0.6 |
50 |
4200 |
|||||
1600 |
2210 |
11370 |
0.75 |
50 |
4900 |
|||||
2000 |
2750 |
14020 |
0.6 |
8 |
52 |
4300 |
||||
2500 |
3240 |
16590 |
0.6 |
52 |
5000 |
SC(B)11 series 20 kv class non – excitation voltage regulator distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
50 |
20 22 24 |
±5 ±2×2.5% |
0.4 |
Dyn11 Yyn0 |
305 |
1070 |
1.8 |
6 |
100 |
485 |
1740 |
1.6 |
|||||
160 |
605 |
2160 |
1.3 |
|||||
200 |
±5% ±2×2.5% |
2570 |
1.3 |
|||||
250 |
760 |
2990 |
1.1 |
|||||
315 |
875 |
3560 |
1.1 |
|||||
400 |
1035 |
4230 |
0.9 |
|||||
500 |
1215 |
5060 |
0.9 |
|||||
630 |
1375 |
5970 |
0.85 |
|||||
800 |
1580 |
7210 |
0.85 |
|||||
1000 |
1860 |
8540 |
0.7 |
|||||
1250 |
2145 |
10040 |
0.7 |
|||||
1600 |
2510 |
12050 |
0.7 |
|||||
2000 |
2915 |
14240 |
0.6 |
|||||
2500 |
3480 |
16860 |
0.6 |
|||||
2000 |
2915 |
15550 |
0.6 |
8 |
||||
2500 |
3480 |
18520 |
0.6 |
SC(B)11 series 35kV class non – excitation voltage regulator distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
50 |
35 36 37 38.5 |
±2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
405 |
1240 |
2.1 |
6.0 |
100 |
570 |
1830 |
1.8 |
|||||
160 |
710 |
2450 |
1.3 |
|||||
200 |
±5 ±2×25% |
2900 |
1.3 |
|||||
250 |
890 |
3320 |
1.1 |
|||||
315 |
1050 |
3940 |
1.1 |
|||||
400 |
1230 |
4720 |
0.9 |
|||||
500 |
1460 |
5810 |
0.9 |
|||||
630 |
1670 |
6720 |
0.8 |
|||||
800 |
1940 |
7970 |
0.8 |
|||||
1000 |
2190 |
9080 |
0.6 |
|||||
1250 |
2550 |
11090 |
0.6 |
|||||
1600 |
2920 |
13450 |
0.6 |
|||||
2000 |
3440 |
15900 |
0.6 |
|||||
2500 |
4000 |
19040 |
0.6 |
SC(B)12 series 10kV class non – excitation voltage regulator distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
30 |
6 6.3 6.6 10 10.5 11 |
±2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
150 |
620 |
1.6 |
4 |
50 |
215 |
880 |
1.6 |
|||||
80 |
295 |
1210 |
1.2 |
|||||
100 |
320 |
1390 |
1.2 |
|||||
125 |
375 |
1630 |
1.1 |
|||||
160 |
430 |
1870 |
1.1 |
|||||
200 |
±2×2.5 |
495 |
2220 |
0.9 |
||||
495 |
575 |
2420 |
0.9 |
|||||
250 |
705 |
3050 |
0.8 |
|||||
315 |
785 |
3500 |
0.8 |
|||||
400 |
930 |
4290 |
0.8 |
|||||
500 |
1040 |
5240 |
0.65 |
6 |
||||
630 |
1215 |
6110 |
0.65 |
|||||
800 |
1415 |
7140 |
0.65 |
|||||
1000 |
1670 |
8510 |
0.65 |
|||||
1250 |
1960 |
10290 |
0.65 |
|||||
1600 |
2440 |
12690 |
0.5 |
|||||
2000 |
2880 |
15080 |
0.5 |
|||||
2500 |
1960 |
11370 |
0.65 |
8 |
||||
1600 |
2440 |
14020 |
0.5 |
|||||
2500 |
2880 |
16590 |
0.5 |
SC(B)13 series 10kV class non – excitation voltage regulator distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
30 |
6 6.3 6.6 10 10.5 11 |
±2.5 ±5 |
0.4 |
Dyn11 Yyn0 |
135 |
560 |
1.4 |
4 |
50 |
195 |
790 |
1.4 |
|||||
80 |
265 |
1080 |
1.1 |
|||||
100 |
290 |
1240 |
1.1 |
|||||
125 |
340 |
1460 |
0.9 |
|||||
160 |
385 |
1670 |
0.9 |
|||||
200 |
±2×2.5 ±5 |
445 |
1990 |
0.8 |
||||
250 |
515 |
2170 |
0.8 |
|||||
315 |
635 |
2730 |
0.7 |
|||||
400 |
705 |
3140 |
0.7 |
|||||
500 |
835 |
3830 |
0.7 |
|||||
630 |
935 |
4690 |
0.6 |
6 |
||||
800 |
1095 |
5470 |
0.6 |
|||||
1000 |
1275 |
6390 |
0.6 |
|||||
1250 |
1505 |
7620 |
0.6 |
|||||
1600 |
1765 |
9220 |
0.6 |
|||||
2000 |
2195 |
11360 |
0.45 |
|||||
2500 |
2590 |
13500 |
0.45 |
|||||
1600 |
1765 |
10190 |
0.6 |
8 |
||||
2000 |
2195 |
12550 |
0.45 |
|||||
2500 |
2590 |
14850 |
0.45 |
Product detail pictures:
Related Product Guide:
Cooperation
Fast and superior quotations, informed advisers to help you choose the correct merchandise that suits all your requirements, a short generation time, responsible quality control and different services for paying and shipping affairs for High Quality Cksc Series Resin Insulation Dry-Type Core Series Reactor - SC(ZB) Series Dry Type Transformer – Pengbian , The product will supply to all over the world, such as: Norway , Kazakhstan , Greece , We only supply quality items and we believe this is the only way to keep business continue. We can supply custom service too such as Logo, custom size, or custom merchandise etc that can according to customer's requirement.
By Olga from Cannes - 2017.08.16 13:39
Sales manager is very enthusiastic and professional, gave us a great concessions and product quality is very good,thank you very much!
By Odelia from Sri Lanka - 2018.06.21 17:11