High Quality for 5000w Step Up And Down Transformer - 35Kv Oil Immersed Transformer – Pengbian
High Quality for 5000w Step Up And Down Transformer - 35Kv Oil Immersed Transformer – Pengbian Detail:
Product standards
GB1094.1~2-2013 GB/T 6451-2015
High pressure rating: 10 (10.5, 11, 6, 6.3, 6.6) kV
Low pressure rating: 0.4 kV
Tapping range: non-field excitation changer
(5% plus or minus 5%, plus or minus 2 x2.)
On-load voltage regulation: (plus or minus 4 x2. 5%)
Link category: Dyn11 or Yyn0
Insulation level: LI75AC35 / AC5
Product parameter
Types of meaning
S11-M series 10kV three – phase double – winding non – excitation voltage regulator distribution transformer
Rated capacity(kVA) |
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
30 |
6 6.3 6.6 10 10.5 11 |
±5X2.5±5 |
0.4 |
Dyn11 Yzn11 YynO |
100 |
630/600 |
1.5 |
4.0 |
50 |
130 |
910/870 |
1.3 |
|||||
63 |
150 |
1090/1040 |
1.2 |
|||||
80 |
180 |
1310/1250 |
1.2 |
|||||
100 |
200 |
1580/1500 |
1.1 |
|||||
125 |
240 |
1890/1800 |
1.1 |
|||||
160 |
280 |
2310/2200 |
1.0 |
|||||
200 |
340 |
2730/2600 |
1.0 |
|||||
250 |
400 |
3200/3050 |
0.90 |
|||||
315 |
480 |
3830/3650 |
0.90 |
|||||
400 |
570 |
4520/4300 |
0.80 |
|||||
500 |
680 |
5410/5150 |
0.80 |
|||||
630 |
Dyn11 YynO |
810 |
6200 |
0.60 |
4.5 |
|||
800 |
980 |
7500 |
0.60 |
|||||
1000 |
1150 |
10300 |
0.60 |
|||||
1250 |
1360 |
12000 |
0.50 |
|||||
1600 |
1640 |
14500 |
0.50 |
|||||
2000 |
1940 |
18300 |
0.40 |
5.0 |
||||
2500 |
2290 |
21200 |
0.40 |
Note 1: For transformers rated 500 kVA or less, the load loss values above the slash in the table apply to the Dyn11 or Yzn11 junction group, and the load loss values below the slash apply to the Yyno junction group.
S11 series 10kV three – phase dual – winding non – excitation voltage regulator power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
630 |
6 6.3 6.6 10 10.5
|
±2X2.5±5 |
3 3.15 6.3 |
Yd11 Dyn11
|
820 |
6920 |
0.6 |
5.5 |
800 |
1000 |
8460 |
0.6 |
|||||
1000 |
1180 |
9910 |
0.6 |
|||||
1250 |
1400 |
11700 |
0.5 |
|||||
1600 |
1680 |
14100 |
0.4 |
|||||
2000 |
2010 |
16900 |
0.4 |
|||||
2500 |
2370 |
19600 |
0.4 |
|||||
3150 |
2800 |
23000 |
0.4 |
|||||
4000 |
3.15 6.3 |
3450 |
27300 |
0.4 |
||||
5000 |
4100 |
31300 |
0.4 |
|||||
6300 |
4890 |
35000 |
0.4 |
SZ11-M series 10kV three-phase double-winding on-load tap-changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
200 |
6 6.3 10 10.5
|
±4X2.5 |
0.4
|
Dyn11 Yyn0
|
380 |
2900 |
1.00 |
4.0 |
250 |
440 |
3420 |
0.90 |
|||||
315 |
530 |
4100 |
0.90 |
|||||
400 |
640 |
4950 |
0.80 |
|||||
500 |
760 |
5890 |
0.80 |
|||||
630 |
960 |
7260 |
0.60 |
4.5 |
||||
800 |
1120 |
8890 |
0.60 |
|||||
1000 |
1360 |
10400 |
0.60 |
|||||
1250 |
1560 |
12300 |
0.50 |
|||||
1600 |
1920 |
14700 |
0.50 |
|||||
2000 |
2270 |
18600 |
0.40 | 5.0 | ||||
2500 |
2680 |
21600 |
0.4 |
Note 1: Rated capacity 500KVA and below transformer, the load loss above the oblique line in the table applies to Dyn11 or Yzn11; the load loss below the oblique line applies to Yyn0.
S11 – M series 20 kv three-phase double-winding non-field excitation changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo(w) |
No-load current (%) |
Short circuit impedance (%) |
No-load current(%) |
Short circuit impedance(%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
30 |
20 22 24
|
±5% ±2×2.5% |
0.4 |
Dyn11 Yzn11 Yyno |
100 |
690/660 |
2.1 |
5.5 |
50 |
130 |
1010/960 |
2 |
|||||
63 |
150 |
1200/1150 |
1.9 |
|||||
80 |
180 |
1440/1370 |
1.8 |
|||||
100 |
200 |
1730/1650 |
1.6 |
|||||
125 |
240 |
2080/1980 |
1.5 |
|||||
160 |
280 |
2540/2420 |
1.4 |
|||||
200 |
340 |
3000/2860 |
1.3 |
|||||
250 |
400 |
3520/3350 |
1.20 |
|||||
315 |
480 |
4210/4010 |
1.10 |
|||||
400 |
570 |
4970/4730 |
1.00 |
|||||
500 |
680 |
5940/5660 |
1.00 |
|||||
630 |
810 |
6820 |
0.90 |
6.0 |
||||
800 |
980 |
8250 |
0.80 |
|||||
1000 |
1150 |
11330 |
0.70 |
|||||
1250 |
1380 |
13200 |
0.70 |
|||||
1600 |
1650 |
15950 |
0.60 |
|||||
2000 |
1950 |
19140 |
0.60 |
|||||
2500 |
2340 |
22220 |
0.50 |
S11 series 35 kv three-phase double-winding non-field excitation changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
50 |
35 38.5 |
±5 ±2×2.5% |
0.4 |
Dyn11 YynO |
160 |
1200/1140 |
1.30 |
6.5 |
100 |
230 |
2010/1910 |
1.10 |
|||||
125 |
270 |
2370/2260 |
1.10 |
|||||
160 |
280 |
2820/2680 |
1.00 |
|||||
200 |
340 |
3320/3160 |
1.00 |
|||||
250 |
400 |
3950/3760 |
0.95 |
|||||
315 |
480 |
4750/4530 |
0.95 |
|||||
400 |
580 |
5740/5470 |
0.85 |
|||||
500 |
680 |
6910/6580 |
0.85 |
|||||
630 |
830 |
7860 |
0.65 |
|||||
800 |
980 |
9400 |
0.65 |
|||||
1000 |
1150 |
11500 |
0.65 |
|||||
1250 |
1400 |
13900 |
0.60 |
|||||
1600 |
1690 |
16600 |
0.60 |
|||||
2000 |
1990 |
19700 |
0.55 |
|||||
2500 |
2360 |
23200 |
0.55 |
Note 1: Rated capacity 500KVA and below transformer, the load loss above the oblique line in the table applies to Dyn11 or Yzn11; the load loss below the oblique line applies to Yyn0.
S11 series 35kV three – phase double – winding group non – excitation voltage regulator power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
50 |
35 38.5 |
±5 ±2×2.5% |
0.4 |
Dyn11 YynO |
160 |
1200/1140 |
1.30 |
6.5 |
100 |
230 |
2010/1910 |
1.10 |
|||||
125 |
270 |
2370/2260 |
1.10 |
|||||
160 |
280 |
2820/2680 |
1.00 |
|||||
200 |
340 |
3320/3160 |
1.00 |
|||||
250 |
400 |
3950/3760 |
0.95 |
|||||
315 |
480 |
4750/4530 |
0.95 |
|||||
400 |
580 |
5740/5470 |
0.85 |
|||||
500 |
680 |
6910/6580 |
0.85 |
|||||
630 |
830 |
7860 |
0.65 |
|||||
800 |
980 |
9400 |
0.65 |
|||||
1000 |
1150 |
11500 |
0.65 |
|||||
1250 |
1400 |
13900 |
0.60 |
|||||
1600 |
1690 |
16600 |
0.60 |
|||||
2000 |
1990 |
19700 |
0.55 |
|||||
2500 |
2360 |
23200 |
0.55 |
Note: For transformers with a low voltage of 10.5 kVA, products with a link group designation of DYn11 are available with a rated capacity of 3150 kvA and above and a -5% tap position for maximum current tapping.
SZ11 series 35kV three – phase double – winding on – load voltage regulator power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
630 |
35 |
±2*2.5% ± 5% |
3.15 6.3 10.5 |
Yd11 |
830 |
7860 |
0.65 |
6.5 |
800 |
980 |
9400 |
0.65 |
|||||
1000 |
1150 |
11500 |
0.65 |
|||||
1250 |
1400 |
13900 |
0.55 |
|||||
1600 |
1690 |
16600 |
0.45 |
|||||
2000 |
2170 |
18300 |
0.45 |
|||||
2500 |
2560 |
19600 |
0.45 |
|||||
3150 |
35-38.5 |
±2X2.5%±5% |
3.15 6.3 10.5 |
3040 |
23000 |
0.45 |
7.0 |
|
4000 |
3610 |
27300 |
0.45 |
|||||
5000 |
4320 |
31300 |
0.45 |
|||||
6300 |
5240 |
35000 |
0.45 |
8.0 |
||||
8000 |
35-38.5 |
±2^2.5% |
3 15 3.3 6.3 6.6 10.5 |
YNd11 |
7200 |
38400 |
0.35 |
|
10000 |
8700 |
45300 |
0.35 |
|||||
12500 |
10000 |
53800 |
0.3 |
|||||
16000 |
12100 |
65800 |
0.3 |
|||||
20000 |
14400 |
79500 |
0.3 |
|||||
25000 |
17000 |
94000 |
0.25 |
10.0 |
||||
31500 |
20200 |
112000 |
0.25 |
Note: for low voltage of 10.5 kVA transformer, can provide link group of products labeled DYn11. – 7.5% tap position for maximum current tap.
35Kv Oil Immersed Transformer Supplier
Zhejiang Pengbian Electric Co., Ltd. is located in China’s electrical capital, is a collection of high-tech at home and abroad in one, the development and production of power transmission equipment key enterprises.
The company has advanced production equipment and exquisite manufacturing technology, specializing in the production of dry type transformer, oil-immersed transformer, special transformer, all kinds of reactor, wind power, photovoltaic transformer substation, substation transformer core, European-style box-type substation, American box transformer substation, high and low voltage complete sets of electrical equipment, power transmission and transformation equipment such as high and low voltage switchgear. Products should be widely in electric power, railway, industrial and mining enterprises, shipping, etc.
Product detail pictures:
Related Product Guide:
Cooperation
Having a positive and progressive attitude to customer's fascination, our organization constantly improves our solution high-quality to fulfill the requirements of shoppers and further focuses on safety, reliability, environmental prerequisites, and innovation of High Quality for 5000w Step Up And Down Transformer - 35Kv Oil Immersed Transformer – Pengbian , The product will supply to all over the world, such as: Spain , Guatemala , Malta , We've got constructed strong and long co-operation relationship with an enormous quantity of companies within this business in Kenya and overseas. Immediate and professional after-sale service supplied by our consultant group has happy our buyers. Thorough Info and parameters from the merchandise will probably be sent for you for any thorough acknowledge. Free samples may be delivered and company check out to our corporation. n Kenya for negotiation is constantly welcome. Hope to get inquiries type you and construct a long-term co-operation partnership.
By Camille from San Francisco - 2017.05.21 12:31
This company has the idea of "better quality, lower processing costs, prices are more reasonable", so they have competitive product quality and price, that's the main reason we chose to cooperate.
By Nana from Sudan - 2018.12.11 11:26