OEM Factory for 5mva Transformer - 35Kv Oil Immersed Transformer – Pengbian
OEM Factory for 5mva Transformer - 35Kv Oil Immersed Transformer – Pengbian Detail:
Product standards
GB1094.1~2-2013 GB/T 6451-2015
High pressure rating: 10 (10.5, 11, 6, 6.3, 6.6) kV
Low pressure rating: 0.4 kV
Tapping range: non-field excitation changer
(5% plus or minus 5%, plus or minus 2 x2.)
On-load voltage regulation: (plus or minus 4 x2. 5%)
Link category: Dyn11 or Yyn0
Insulation level: LI75AC35 / AC5
Product parameter
Types of meaning
S11-M series 10kV three – phase double – winding non – excitation voltage regulator distribution transformer
Rated capacity(kVA) |
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
30 |
6 6.3 6.6 10 10.5 11 |
±5X2.5±5 |
0.4 |
Dyn11 Yzn11 YynO |
100 |
630/600 |
1.5 |
4.0 |
50 |
130 |
910/870 |
1.3 |
|||||
63 |
150 |
1090/1040 |
1.2 |
|||||
80 |
180 |
1310/1250 |
1.2 |
|||||
100 |
200 |
1580/1500 |
1.1 |
|||||
125 |
240 |
1890/1800 |
1.1 |
|||||
160 |
280 |
2310/2200 |
1.0 |
|||||
200 |
340 |
2730/2600 |
1.0 |
|||||
250 |
400 |
3200/3050 |
0.90 |
|||||
315 |
480 |
3830/3650 |
0.90 |
|||||
400 |
570 |
4520/4300 |
0.80 |
|||||
500 |
680 |
5410/5150 |
0.80 |
|||||
630 |
Dyn11 YynO |
810 |
6200 |
0.60 |
4.5 |
|||
800 |
980 |
7500 |
0.60 |
|||||
1000 |
1150 |
10300 |
0.60 |
|||||
1250 |
1360 |
12000 |
0.50 |
|||||
1600 |
1640 |
14500 |
0.50 |
|||||
2000 |
1940 |
18300 |
0.40 |
5.0 |
||||
2500 |
2290 |
21200 |
0.40 |
Note 1: For transformers rated 500 kVA or less, the load loss values above the slash in the table apply to the Dyn11 or Yzn11 junction group, and the load loss values below the slash apply to the Yyno junction group.
S11 series 10kV three – phase dual – winding non – excitation voltage regulator power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
630 |
6 6.3 6.6 10 10.5
|
±2X2.5±5 |
3 3.15 6.3 |
Yd11 Dyn11
|
820 |
6920 |
0.6 |
5.5 |
800 |
1000 |
8460 |
0.6 |
|||||
1000 |
1180 |
9910 |
0.6 |
|||||
1250 |
1400 |
11700 |
0.5 |
|||||
1600 |
1680 |
14100 |
0.4 |
|||||
2000 |
2010 |
16900 |
0.4 |
|||||
2500 |
2370 |
19600 |
0.4 |
|||||
3150 |
2800 |
23000 |
0.4 |
|||||
4000 |
3.15 6.3 |
3450 |
27300 |
0.4 |
||||
5000 |
4100 |
31300 |
0.4 |
|||||
6300 |
4890 |
35000 |
0.4 |
SZ11-M series 10kV three-phase double-winding on-load tap-changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
200 |
6 6.3 10 10.5
|
±4X2.5 |
0.4
|
Dyn11 Yyn0
|
380 |
2900 |
1.00 |
4.0 |
250 |
440 |
3420 |
0.90 |
|||||
315 |
530 |
4100 |
0.90 |
|||||
400 |
640 |
4950 |
0.80 |
|||||
500 |
760 |
5890 |
0.80 |
|||||
630 |
960 |
7260 |
0.60 |
4.5 |
||||
800 |
1120 |
8890 |
0.60 |
|||||
1000 |
1360 |
10400 |
0.60 |
|||||
1250 |
1560 |
12300 |
0.50 |
|||||
1600 |
1920 |
14700 |
0.50 |
|||||
2000 |
2270 |
18600 |
0.40 | 5.0 | ||||
2500 |
2680 |
21600 |
0.4 |
Note 1: Rated capacity 500KVA and below transformer, the load loss above the oblique line in the table applies to Dyn11 or Yzn11; the load loss below the oblique line applies to Yyn0.
S11 – M series 20 kv three-phase double-winding non-field excitation changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo(w) |
No-load current (%) |
Short circuit impedance (%) |
No-load current(%) |
Short circuit impedance(%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
30 |
20 22 24
|
±5% ±2×2.5% |
0.4 |
Dyn11 Yzn11 Yyno |
100 |
690/660 |
2.1 |
5.5 |
50 |
130 |
1010/960 |
2 |
|||||
63 |
150 |
1200/1150 |
1.9 |
|||||
80 |
180 |
1440/1370 |
1.8 |
|||||
100 |
200 |
1730/1650 |
1.6 |
|||||
125 |
240 |
2080/1980 |
1.5 |
|||||
160 |
280 |
2540/2420 |
1.4 |
|||||
200 |
340 |
3000/2860 |
1.3 |
|||||
250 |
400 |
3520/3350 |
1.20 |
|||||
315 |
480 |
4210/4010 |
1.10 |
|||||
400 |
570 |
4970/4730 |
1.00 |
|||||
500 |
680 |
5940/5660 |
1.00 |
|||||
630 |
810 |
6820 |
0.90 |
6.0 |
||||
800 |
980 |
8250 |
0.80 |
|||||
1000 |
1150 |
11330 |
0.70 |
|||||
1250 |
1380 |
13200 |
0.70 |
|||||
1600 |
1650 |
15950 |
0.60 |
|||||
2000 |
1950 |
19140 |
0.60 |
|||||
2500 |
2340 |
22220 |
0.50 |
S11 series 35 kv three-phase double-winding non-field excitation changer distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
50 |
35 38.5 |
±5 ±2×2.5% |
0.4 |
Dyn11 YynO |
160 |
1200/1140 |
1.30 |
6.5 |
100 |
230 |
2010/1910 |
1.10 |
|||||
125 |
270 |
2370/2260 |
1.10 |
|||||
160 |
280 |
2820/2680 |
1.00 |
|||||
200 |
340 |
3320/3160 |
1.00 |
|||||
250 |
400 |
3950/3760 |
0.95 |
|||||
315 |
480 |
4750/4530 |
0.95 |
|||||
400 |
580 |
5740/5470 |
0.85 |
|||||
500 |
680 |
6910/6580 |
0.85 |
|||||
630 |
830 |
7860 |
0.65 |
|||||
800 |
980 |
9400 |
0.65 |
|||||
1000 |
1150 |
11500 |
0.65 |
|||||
1250 |
1400 |
13900 |
0.60 |
|||||
1600 |
1690 |
16600 |
0.60 |
|||||
2000 |
1990 |
19700 |
0.55 |
|||||
2500 |
2360 |
23200 |
0.55 |
Note 1: Rated capacity 500KVA and below transformer, the load loss above the oblique line in the table applies to Dyn11 or Yzn11; the load loss below the oblique line applies to Yyn0.
S11 series 35kV three – phase double – winding group non – excitation voltage regulator power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
50 |
35 38.5 |
±5 ±2×2.5% |
0.4 |
Dyn11 YynO |
160 |
1200/1140 |
1.30 |
6.5 |
100 |
230 |
2010/1910 |
1.10 |
|||||
125 |
270 |
2370/2260 |
1.10 |
|||||
160 |
280 |
2820/2680 |
1.00 |
|||||
200 |
340 |
3320/3160 |
1.00 |
|||||
250 |
400 |
3950/3760 |
0.95 |
|||||
315 |
480 |
4750/4530 |
0.95 |
|||||
400 |
580 |
5740/5470 |
0.85 |
|||||
500 |
680 |
6910/6580 |
0.85 |
|||||
630 |
830 |
7860 |
0.65 |
|||||
800 |
980 |
9400 |
0.65 |
|||||
1000 |
1150 |
11500 |
0.65 |
|||||
1250 |
1400 |
13900 |
0.60 |
|||||
1600 |
1690 |
16600 |
0.60 |
|||||
2000 |
1990 |
19700 |
0.55 |
|||||
2500 |
2360 |
23200 |
0.55 |
Note: For transformers with a low voltage of 10.5 kVA, products with a link group designation of DYn11 are available with a rated capacity of 3150 kvA and above and a -5% tap position for maximum current tapping.
SZ11 series 35kV three – phase double – winding on – load voltage regulator power transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbo |
No-load loss (W) |
Load loss (w) |
No-load current (%) |
Short circuit impedance (%) |
||
High pressure |
High pressure tap range (%) |
Low pressure (kV) |
||||||
630 |
35 |
±2*2.5% ± 5% |
3.15 6.3 10.5 |
Yd11 |
830 |
7860 |
0.65 |
6.5 |
800 |
980 |
9400 |
0.65 |
|||||
1000 |
1150 |
11500 |
0.65 |
|||||
1250 |
1400 |
13900 |
0.55 |
|||||
1600 |
1690 |
16600 |
0.45 |
|||||
2000 |
2170 |
18300 |
0.45 |
|||||
2500 |
2560 |
19600 |
0.45 |
|||||
3150 |
35-38.5 |
±2X2.5%±5% |
3.15 6.3 10.5 |
3040 |
23000 |
0.45 |
7.0 |
|
4000 |
3610 |
27300 |
0.45 |
|||||
5000 |
4320 |
31300 |
0.45 |
|||||
6300 |
5240 |
35000 |
0.45 |
8.0 |
||||
8000 |
35-38.5 |
±2^2.5% |
3 15 3.3 6.3 6.6 10.5 |
YNd11 |
7200 |
38400 |
0.35 |
|
10000 |
8700 |
45300 |
0.35 |
|||||
12500 |
10000 |
53800 |
0.3 |
|||||
16000 |
12100 |
65800 |
0.3 |
|||||
20000 |
14400 |
79500 |
0.3 |
|||||
25000 |
17000 |
94000 |
0.25 |
10.0 |
||||
31500 |
20200 |
112000 |
0.25 |
Note: for low voltage of 10.5 kVA transformer, can provide link group of products labeled DYn11. – 7.5% tap position for maximum current tap.
35Kv Oil Immersed Transformer Supplier
Zhejiang Pengbian Electric Co., Ltd. is located in China’s electrical capital, is a collection of high-tech at home and abroad in one, the development and production of power transmission equipment key enterprises.
The company has advanced production equipment and exquisite manufacturing technology, specializing in the production of dry type transformer, oil-immersed transformer, special transformer, all kinds of reactor, wind power, photovoltaic transformer substation, substation transformer core, European-style box-type substation, American box transformer substation, high and low voltage complete sets of electrical equipment, power transmission and transformation equipment such as high and low voltage switchgear. Products should be widely in electric power, railway, industrial and mining enterprises, shipping, etc.
Product detail pictures:
Related Product Guide:
Cooperation
abide by the contract", conforms on the market requirement, joins from the market competition by its good quality likewise as provides more comprehensive and superb support for customers to let them become large winner. The pursue of the company, is definitely the clients' pleasure for OEM Factory for 5mva Transformer - 35Kv Oil Immersed Transformer – Pengbian , The product will supply to all over the world, such as: Portland , Eindhoven , Philippines , Due to our strict pursues in quality, and after-sale service, our product gets more and more popular around the world. Many clients came to visit our factory and place orders. And there are also many foreign friends who came for sight seeing, or entrust us to buy other stuff for them. You are most welcome to come to China, to our city and to our factory!
By Irma from Czech republic - 2018.09.29 17:23
Factory equipment is advanced in the industry and the product is fine workmanship, moreover the price is very cheap, value for money!
By Daphne from Hungary - 2018.12.25 12:43