SBH15 10KV Immersed Amorphous Alloy Core Distribution Transformers
Features
Energy Saving, No-load Loss Is 75% Less Than S9 Series;
Low Loss, Low Noise, Low Temperature Rise, Steady Work;
Advanced Structure, High Anti Short Circuit;
High Overload Ability, Safe And Reliable, High Resistant To Corrosion, Free Maintenance.
Product parameter
Types of meaning
Product standards
GB1094.1 ~ 2-2013 GB/T 25446-2010
High pressure rating: 10 (10.5, 11, 6, 6.3, 6.6) kV
Low pressure rating: 0.4 kV
Tapping range: non-field excitation changer (plus or minus 5%, plus or minus 2 x2.5% )
Link category: Dyn11 or Yyno
Insulation level: LI75AC35 / AC5
S(B)H15-M series 10 kv three-phase double winding excitation regulating distribution transformer
Rated capacity(kVA) |
Voltage Combinationand Tap range |
Vector Group Symbol |
No-load loss (W) |
Load loss |
No-load current (%) |
Short circuit impedance (%) 4.0 |
||
High pressure |
High pressure tap range (%) |
Low ressure (kV) |
||||||
30 |
6 6.3 10 10.5 11 |
±2X2.5±5 |
0.4 |
Dyn11 YynO |
33 |
630/660 |
1.5 |
4.0 |
50 |
43 |
910V870 |
1.2 |
|||||
63 |
50 |
1090/1040 |
1.1 |
|||||
80 |
60 |
1310/1250 |
1.0 |
|||||
100 |
75 |
1580/1500 |
0.90 |
|||||
125 |
85 |
1890/1800 |
0.80 |
|||||
160 |
100 |
2310/2200 |
0.60 |
|||||
200 |
120 |
2730/2600 |
0.60 |
|||||
250 |
140 |
3200/3050 |
0.60 |
|||||
315 |
170 |
3830/3650 |
0.50 |
|||||
400 |
200 |
4520/4300 |
0.50 |
|||||
500 |
200 |
5410/5150 |
0.60 |
|||||
630 |
320 |
6200 |
0.30 |
4.5 |
||||
800 |
380 |
7500 |
0.30 |
|||||
1000 |
450 |
10300 |
0.30 |
|||||
1250 |
530 |
12000 |
0.20 |
|||||
1600 |
630 |
14500 |
0.20 |
|||||
2000 |
750 |
18300 |
0.20 |
5.0 |
||||
2500 |
900 |
21200 |
0.20 |
Note: for the rated capacity of 500 kva and below transformer, load loss value of the diagonal lines in the table above apply to Dyn11 or Yzn11 link group, slash at the bottom of the load loss value applies to Yyno link group.
Product outline drawing